Aprilaire 8570 Specifikace Strana 23

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 25
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 22
7. INPUT DEALER CONTACT INFORMATION
During thermostat operation, the two multi-function buttons
are labeled INFO and MENU. When the INFO button is
pressed, the thermostat will display the humidity and
temperature sensed by the ADHC (if an ADHC has been
installed), then the thermostat will display any monitor
messages and dealer contact information. At installation,
the contact information is blank and only the thermostat
model number appears. You have the option of inputting this
contact information with the name and number of your
company. Three twenty (20) character lines are available for
your company name and contact info.
To change the contact information:
1. Make sure the thermostat is in the OFF mode.
2. Press and hold both the and buttons for 3 seconds.
– The display will show the ADV. SETTINGS MENU.
3. Use the or button to highlight “INPUT DEALER INFO”
and press the SELECT button. This enters Line 1.
4. To cancel, press the BACK button. This returns to the
ADV. SETTINGS MENU. You must be at the first position
when pressing the BACK button to return to the
ADV. SETTINGS MENU.
5. To go back a character, press the BACK button.
6. To enter a character, use the or buttons to scroll
through the available characters. Press the SELECT button
to enter the character.
7. To finish Line 1 and go to Line 2, repeatedly press
SELECT, filling all remaining characters with spaces,
then press SELECT again.
8. Repeat to fill Line 2 and Line 3.
9. To finish, press the SELECT button after entering the
20th character of the third line.
- 41 -- 40 -
6. BALANCE POINTS (HEAT PUMPS ONLY)
This feature is only available when the thermostat has been
configured to operate heat pumps (see SET THE
CONFIGURATION DIP SWITCHES on page 6) and only when an
outdoor temperature is available to the thermostat. Outdoor
temperature can come from an ADHC or from an outdoor
temperature sensor.
The low balance point is the outdoor temperature at or below
which the thermostat will lockout the compressor(s) – only
auxiliary heat will be used to satisfy heating demands. The high
balance point is the outdoor temperature at or above which the
thermostat will lockout the auxiliary heat – only compressor
heat will be used to satisfy heating demands. Emergency heat
operation is unaffected by the high balance point.
To change the balance points:
1. Make sure the thermostat is in the OFF mode.
2. Press and hold both the and buttons for 3 seconds.
– The display will show the ADV. SETTINGS MENU.
3. Use the or button to highlight “SET BALANCE
POINTS” and press the SELECT button.
4. To cancel, press the BACK button. This will return you to
the ADV. SETTINGS MENU.
5. To change the low balance point, press the or
button to raise or lower the temperature value
(range is -10°F to 35°F and OFF).
6. To change the high balance point, press the SELECT
button, then press the or button to raise or lower the
temperature value (range is 40°F to 80°F and OFF).
7. To finish and return to the ADV. SETTINGS MENU, press
the SELECT button after the value(s) have been set.
Important time saver: If the thermostat is installed as part
of a Model 6504 Intelligent Zoned Comfort System, the
balance points only need to be changed at one thermostat.
The Model 6504 will share the new settings with all
connected thermostats.
Zobrazit stránku 22
1 2 ... 18 19 20 21 22 23 24 25

Komentáře k této Příručce

Žádné komentáře